Formulas

Resistance and Series Reactance

The impedance Z of a reactive load comprising resistance R and series reactance X is:

Z = R + jX = |Z|Ðf

Converting to the equivalent admittance Y:

Y = 1 / Z = 1 / (R + jX) = (R – jX) / (R2 + X2) = R / |Z|2 – jX / |Z|2

When a voltage V (taken as reference) is applied across the reactive load Z, the current I is:

I = VY = V(R / |Z|2 – jX / |Z|2) = VR / |Z|2 – jVX / |Z|2 = IP – jIQ

The active current IP and the reactive current IQ are:

IP = VR / |Z|2 = |I|cosf

IQ = VX / |Z|2 = |I|sinf

The apparent power S, active power P and reactive power Q are:

S = V|I| = V2 / |Z| = |I|2|Z|

P = VIP = IP2|Z|2 / R = V2R / |Z|2 = |I|2R

Q = VIQ = IQ2|Z|2 / X = V2X / |Z|2 = |I|2X

The power factor cosf and reactive factor sinf are:

cosf = IP / |I| = P / S = R / |Z|

sinf = IQ / |I| = Q / S = X / |Z|

Resistance and Shunt Reactance

The impedance Z of a reactive load comprising resistance R and shunt reactance X is found from:

1 / Z = 1 / R + 1 / jX

Converting to the equivalent admittance Y comprising conductance G and shunt susceptance B:

Y = 1 / Z = 1 / R – j / X = G – jB = |Y|Ð-f

When a voltage V (taken as reference) is applied across the reactive load Y, the current I is:

I = VY = V(G – jB) = VG – jVB = IP – jIQ

The active current IP and the reactive current IQ are:

IP = VG = V / R = |I|cosf

IQ = VB = V / X = |I|sinf

The apparent power S, active power P and reactive power Q are:

S = V|I| = |I|2 / |Y| = V2|Y|

P = VIP = IP2 / G = |I|2G / |Y|2 = V2G

Q = VIQ = IQ2 / B = |I|2B / |Y|2 = V2B

The power factor cosf and reactive factor sinf are:

cosf = IP / |I| = P / S = G / |Y|

sinf = IQ / |I| = Q / S = B / |Y|

NOTATION
The symbol font is used for some notation and formulae. If the Greek symbols for alpha beta delta do not appear here [ a b d ] the symbol font needs to be installed for correct display of notation and formulae.
B
C
E
f
G
h
I
j
L
P
Q
susceptance
capacitance
voltage source
frequency
conductance
h-operator
current
j-operator
inductance
active power
reactive power
[siemens, S]
[farads, F]
[volts, V]
[hertz, Hz]
[siemens, S]
[1Ð120°]
[amps, A]
[1Ð90°]
[henrys, H]
[watts, W]
[VAreactive, VArs]
Q
R
S
t
V
W
X
Y
Z
f
w
quality factor
resistance
apparent power
time
voltage drop
energy
reactance
admittance
impedance
phase angle
angular frequency
[number]
[ohms, W]
[volt-amps, VA]
[seconds, s]
[volts, V]
[joules, J]
[ohms, W]
[siemens, S]
[ohms, W]
[degrees, °]
[rad/sec]

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information

Leave a Comment

Tell us what you're thinking... we care about your opinion!

Subscribe to Weekly Digest

Get email alert whenever we publish new electrical guides and articles.

New Online Training Courses

World class online training for electrical engineers and industrial electricians.