The synchronous rotational speed ns and synchronous angular speed ws of a machine with p pole pairs running on a supply of frequency fs are:
ns = 60fs / p
ws = 2pfs / p = 2pns / 60

The per-unit slip s of an induction machine of synchronous rotational speed ns running at rotational speed nm is:
s = (ns – nm) / ns
Rearranging for rotational speed nm:
nm = (1 – s)ns
Using angular speed w instead of rotational speed n:
wm = (1 – s)ws

The rated load torque TM for a rated output power PM is:
TM = PM / wm = 60PM / 2pnm

For an induction machine with Ns stator turns and Nr rotor turns running at slip s on a supply of voltage Es and frequency fs, the rotor induced voltage and frequency Er and fr are:
Er = sEsNr / Ns
fr = sfs
For a rotor current Ir, the equivalent stator current Irs is:
Irs = IrNr / Ns
Note that the rotor / stator ratios are Ns / Nr for current, sNr / Ns for voltage and s for frequency.

For an induction machine with rotor resistance Rr and locked rotor leakage reactance Xr, the rotor impedance Zr at slip s is:
Zr = Rr + jsXr
The stator circuit equivalent impedance Zrf for a rotor / stator frequency ratio s is:
Zrf = Rrs / s + jXrs

For an induction motor with synchronous angular speed ws running at angular speed wm and slip s, the airgap transfer power Pt, rotor copper loss Pr and gross output power Pm for a gross output torque Tm are related by:
Pt = wsTm = Pr / s = Pm / (1 – s)
Pr = sPt = sPm / (1 – s)
Pm = wmTm = (1 – s)Pt
The power ratios are:
Pt : Pr : Pm = 1 : s : (1 – s)
The gross motor efficiency hm (neglecting stator and mechanical losses) is:
hm = Pm / Pt = 1 – s

An induction machine can be operated as a generator, a motor or a brake:

  • for negative slip (speed above synchronous) the machine is a generator,
  • for positive slip between 0 and 1 (speed below synchronous) the machine is a motor,
  • for positive slip greater than 1 (speed negative) the machine is a brake,

In all cases the magnetizing current (at lagging power factor) is provided by the supply system.

No Load Test
If an induction machine with its rotor unloaded is energised at rated voltage, then the input power represents the sum of the iron loss and mechanical loss of the machine.

Locked Rotor Test
If an induction machine with its rotor locked is energised at a reduced voltage which causes rated current input, then the input power represents the sum of the full load copper loss and stray loss of the machine.

Stator Resistance Test
The resistance of the stator winding is measured using a small direct current.

Formulas

NOTATION
The symbol font is used for some notation and formulae. If the Greek symbols for alpha beta delta do not appear here [ a b d ] the symbol font needs to be installed for correct display of notation and formulae.
B
E
f
G
I
j
k
m
N
n
P
p
R
susceptance
induced voltage
frequency
conductance
current
j-operator
coefficient
number of phases
number of turns
rotational speed
power
pole pairs
resistance
[siemens, S]
[volts, V]
[hertz, Hz]
[siemens, S]
[amps, A]
[1Ð90°]
[number]
[number]
[number]
[revs/min]
[watts, W]
[number]
[ohms, W]
S
s
T
V
X
Y
Z
d
F
f
h
q
w
voltamperes
slip
torque
terminal voltage
reactance
admittance
impedance
loss angle
magnetic flux
phase angle
efficiency
temperature
angular speed
[volt-amps, VA]
[per-unit]
[newton-metres, Nm]
[volts, V]
[ohms, W]
[siemens, S]
[ohms, W]
[degrees, °]
[webers, Wb]
[degrees, °]
[per-unit]
[centigrade, °C]
[radians/sec]

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

One Comment


  1. Nguyễn Hoàng Vũ
    Aug 10, 2022

    I want to have magazines about control speed for induction motors!.

Leave a Reply to Nguyễn Hoàng Vũ

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  ×  6  =  fifty four

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Courses - A hand crafted cutting-edge electrical engineering knowledge