Shunt Reactors

For star-connected shunt reactors each of inductance Lstar on a three phase system of line voltage Vline and frequency f, the lagging reactive power demand QLstar and the lagging reactive line current Iline are:

QLstar = Vline2 / XLstar = Vline2 / 2pfLstar

Iline = QLstar / Ö3Vline = Vline / Ö3XLstar

Lstar = Vline2 / 2pfQLstar

For delta-connected shunt reactors each of inductance Ldelta on a three phase system of line voltage Vline and frequency f, the lagging reactive power demand QLdelta and the lagging reactive line current Iline are:

QLdelta = 3Vline2 / XLdelta = 3Vline2 / 2pfLdelta

Iline = QLdelta / Ö3Vline = Ö3Vline / XLdelta

Ldelta = 3Vline2 / 2pfQLdelta

Note that for the same lagging reactive power QL:

XLdelta = 3XLstar

Ldelta = 3Lstar

Series Reactors

For series line reactors each of inductance Lseries carrying line current Iline on a three phase system of frequency f, the voltage drop Vdrop across each line reactor and the total lagging reactive power demand QLseries of the set of three line reactors are:

Vdrop = IlineXLseries = 2pfLseriesIline

QLseries = 3Vdrop2 / XLseries = 3VdropIline = 3Iline2XLseries = 6pfLseriesIline2

Lseries = QLseries / 6pfIline2

Note that the apparent power rating Srating of the set of three series line reactors is based on the line voltage Vline and not the voltage drop Vdrop:

Srating = Ö3VlineIline

NOTATION
The symbol font is used for some notation and formulae. If the Greek symbols for alpha beta delta do not appear here [ a b d ] the symbol font needs to be installed for correct display of notation and formulae.
B
C
E
f
G
h
I
j
L
P
Q
susceptance
capacitance
voltage source
frequency
conductance
h-operator
current
j-operator
inductance
active power
reactive power
[siemens, S]
[farads, F]
[volts, V]
[hertz, Hz]
[siemens, S]
[1Ð120°]
[amps, A]
[1Ð90°]
[henrys, H]
[watts, W]
[VAreactive, VArs]
Q
R
S
t
V
W
X
Y
Z
f
w
quality factor
resistance
apparent power
time
voltage drop
energy
reactance
admittance
impedance
phase angle
angular frequency
[number]
[ohms, W]
[volt-amps, VA]
[seconds, s]
[volts, V]
[joules, J]
[ohms, W]
[siemens, S]
[ohms, W]
[degrees, °]
[rad/sec]

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

2 Comments


  1. Roberto
    Jul 06, 2023

    There is a mistake in one formula of the series reactor: QLseries = Vdrop^2 / XLseries. Remove the factor “3”.


  2. umesh yadav
    Jan 01, 2018

    IS TOLERENCE OF VOLTAGE DROP IN THREE PHASE SERIES REACTOR ?

Leave a Comment

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

48  ⁄    =  sixteen

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.