Search

Premium Membership

Study specialized technical articles, papers & video courses in low/high voltage areas. Save 50% on all courses at the EEP Academy with the Enterprise Plan.

Home / Technical Articles / Surge protective categories defined by ANSI/IEEE C62.41
Surge protective categories defined by ANSI/IEEE C62.41
Surge protective categories defined by ANSI/IEEE C62.41 (on photo: New VPU surge voltage protection devices from Weidmüller)

ANSI/IEEE C62.41

Three different surge protective classes or zones have been defined by ANSI/IEEE C62.41, Recommended Practice on Surge Voltages in Low Voltage Power Circuits.

These classes are illustrated in the pictorial diagram Fig. 12-1.


Category C (outdoors)

Category C (outdoors) is the region outside the home or building that includes external conductors, and it extends inside to the load center main circuit breaker or service entrance disconnect breaker.

It is expected that surges originating outside the building could enter it by way of the service drop from the pole to the building through the watthour meter busbars to the circuit breakers, as well as from other overhead and underground conductors.

Studies have shown that the highest-magnitude natural and man made surge currents and voltages originate in this Category C zone.

Examples of these include lightning strikes on or near power lines and surges set up by the switching or failure of power company generators or other equipment. Both of these sources cause energy surges to be coupled into the building by induction. Consequently, the best surge protection is afforded by surge protective devices (SPDs), sized to withstand high-magnitude surges, that are installed ahead of service entrance disconnect circuit breakers.


Category B (indoors)

Category B (indoors) is a zone within a residence or building that extends at least 30 ft (10 m) from the service entrance disconnect breaker along feeders or branch circuits to electrical receptacles or outlets.

As stated previously, the most probable sources of surges within this zone are the on/off switching of electric motors or motordriven appliances. Other sources are high-voltage or high-frequency medical and scientific apparatus located close to the structure being protected.

This equipment is installed in hospitals, private diagnostic facilities, and research laboratories.

Consequently, all SPDs installed in the B zone should be sized to withstand the largest-magnitude surges expected from all of these sources.


Category A (indoors)

Category A (indoors) is the zone farthest from the disconnect breaker.

It is defined as the zone within the building where the branch circuits extend to all outlets that are more than 30 ft (10 m) from Category B outlets, and more than 60 ft (20 m) from the service entrance disconnect breaker located in the Category C zone.

Surge protective operating environments as defined by ANSI/IEEE C62.41
Figure 1 - Surge protective operating environments as defined by ANSI/IEEE C62.41

Category C: Outside and service entrances (line side)

  1. Service drops from pole to building
  2. Conducted between meter and disconnect breaker
  3. Overhead lines to nearby buildings

Category B: Feeders and short branch circuits (line side)

  1. Distribution panel equipment
  2. Short branch circuits and feeder lines

Category A: Branch circuits and outlets distant from Categories B and C

  1. Outlets > 30 ft (10 m) from Category B boundary
  2. Outlets > 60 ft (20 m) from Category C boundary

Exposure levels

ANSI/IEEE C62.41 defines the three exposure levels that characterize the rate of surge occurrence versus voltage level at an unprotected site as follows:

Low

Geographic locations where lightning activity is known to be low, and little load switching is anticipated.

Medium

Geographic locations where medium to high lightning activity is expected, significant load switching is anticipated, or both.

High

Geographic locations where surges greater than those defined as low or medium are expected.

Reference: Handbook of electrical design details // Second edition – Neil Sclater; John E. Traister
(Purchase ebook)

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry facilities. Professional in AutoCAD programming.

2 Comments


  1. Ashish Gehlot
    Jul 02, 2021

    Keen to have more storey on power quality equipment’s & speciality transformers


  2. Samaresh Ghorai
    Apr 15, 2016

    MOV selection calculation for over voltage protection in house.

Leave a Reply to Samaresh Ghorai

Tell us what you're thinking... we care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  ⁄  one  =  5

EEP Academy Video Courses

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning.