Main substations installed on public MV network, their functions and layout
This technical article is a reminder of the main substations installed on MV networks. It is concluded by two layouts showing their applications in real terms. A substation or installation is a physical entity defined by its position and its… Read more
Mar 18, 2016 | By Edvard Csanyi
Practical Considerations of LV/MV Private Substations
Private substations can often be considered as terminal type substations, i.e. substations where the MV line ends at the point of installation of the substation itself. They belong to the user and can supply both civil users (schools, hospitals, etc.)… Read more
Mar 04, 2016 | By Edvard Csanyi
5 good circuit schemes to avoid HV substation outage
High voltage substations are points in the power system where power can be pooled from generating sources, distributed and transformed, and delivered to the load points. Substations are interconnected with each other so that the power system becomes a meshed… Read more
Jan 02, 2016 | By Edvard Csanyi
Distribution of the MV neutral conductor right to the loads
4-wire systems are characterized by distribution of the MV neutral conductor right to the loads. This type of distribution is used in the USA and in certain countries influenced by North America, and is always subject to ANSI regulations. It… Read more
Dec 16, 2015 | By Edvard Csanyi
Single-line diagram of the AC transmission and distribution system
The conductor system by means of which electric power is conveyed from a generating station to the consumer’s premises may, in general, be divided into two distinct parts i.e. transmission system and distribution system. Each part can again be sub-divided… Read more
Nov 13, 2015 | By Edvard Csanyi
6 Voltages a Person Can Be Exposed To In a Substation
Figures 1 and 2 show the voltages a person can be exposed to in a substation. There are many definitions related to these voltages, but the following six are the most important. These definitions are: Ground potential rise (GPR) Mesh… Read more
Oct 09, 2015 | By Edvard Csanyi
The Basics Of Distribution Substations For Electrical Engineers (Beginners)
Distribution substations serve a wide range of private and public customers in distributing electric power. They can be shareholder, cooperatively, privately, and government owned. All substations contain power transformers and the voltage-regulating apparatus required for converting the high incoming sub-transmission… Read more
Oct 07, 2015 | By Edvard Csanyi
Substation AC Auxiliary Supply For Inessential Loads
The purpose of auxiliary power supply systems is to cater for the necessary energy for the operation of primary and secondary devices at the substation. The auxiliary power systems are normally divided in two categories, namely the AC system and… Read more
Sep 30, 2015 | By Edvard Csanyi
Substation DC Auxiliary Supply – Battery And Charger Applications
A power substation can have one or several DC systems. Factors affecting the number of systems are the need for more than one voltage level and the need for duplicating systems. Today, normal DC auxiliary supply systems in power substations are… Read more
Sep 21, 2015 | By Edvard Csanyi
6 Transformer Types You Can See In Commercial Installations
Transformers in commercial installations are normally used to change a voltage level from a utility distribution voltage to a voltage that is usable within the building, and are also used to reduce building distribution voltage to a level that can… Read more
Mar 16, 2015 | By Edvard Csanyi
The consumer power substation with metering on medium voltage side
A consumer power substation with metering on medium voltage side is an electrical installation connected to a utility supply system at a nominal voltage usually between 1kV – 35kV, which for example may supply a single MV/LV transformer (exceeding generally 1250… Read more
Jan 12, 2015 | By Edvard Csanyi
Main and Transfer (Inspection) Bus Arrangement commonly used in AIS
The main and transfer bus configuration connects all circuits between the main bus and a transfer bus (sometimes referred to as an inspection bus). Some arrangements include a bus tie breaker and others simply utilize switches for the tie between… Read more
Aug 13, 2014 | By Edvard Csanyi
What engineers should know about using conduits in power substation designs
There are several locations where conduit is used in power substation designs. The most common one considered is conduit used to provide cable access to equipment, such as breakers, transformers, instrument transformers, and motor-operated disconnect switches located in the yard… Read more
Jul 25, 2014 | By Edvard Csanyi
Instrument transformers (CTs, VTs) in the system
The three main tasks of instrument transformers are: To transform currents or voltages from a usually high value to a value easy to handle for relays and instruments. To insulate the metering circuit from the primary high voltage system. To provide… Read more
May 19, 2014 | By Edvard Csanyi
Comparison of major power grid failures in US and around the world (2)
Continued from first part: Comparison of major grid failures in United States and around the world (part 1) On the International side, about 1/5 of the power outages (9 of 44) were not given a cause in the reports. A… Read more
Dec 27, 2013 | By Edvard Csanyi
