Best practice for using surge protective devices (SPDs) and RCD together
Where the power distribution system incorporates RCDs transient activity could cause RCDs to operate and hence loss of supply. Surge protective devices (SPDs) should wherever possible be installed upstream of RCD to prevent unwanted tripping caused by transient overvoltages. Where… Read more
Oct 07, 2016 | By Edvard Csanyi
4 steps to diagnose a potential harmonics related problem
If a plant engineer suspects that he might have a harmonics related problem, the following steps can easily be performed as an initial investigation into potential problems: Look for symptoms of harmonics as listed in Table 1 below. If one… Read more
Oct 05, 2016 | By Edvard Csanyi
Problems with audible substation noise and what you can do about it
Audible substation noise, particularly continuously radiated discrete tones (e.g., from power transformers), is the type of noise that the community may find unacceptable. Community guidelines to ensure that acceptable substation noise levels are maintained can take the form of governmental… Read more
Oct 03, 2016 | By Edvard Csanyi
Advice how to calculate the power loss inside the low voltage switchboard
In order to give the necessary indications on the methods intended to calculate power loss and improve the current carrying capacity of the circuit breakers inside LV switchboard, first of all it is necessary to analyze an assembly from a… Read more
Sep 30, 2016 | By Edvard Csanyi
6 transformer operating limitations that make it far from ideal
There are few operating limitations that make transformer far from ideal. Generally, some of transformer operating limitations can be minimized, but not in total, never in total. Let’s talk about these limitations. Transformer losses (Heat) Copper (or winding) losses Iron… Read more
Sep 28, 2016 | By Edvard Csanyi
7 typical layout designs of 11kV indoor distribution substation
The following layout designs of indoor distribution substation are typical only and should not be used as construction drawings as they are presented as an example. Some designs achieve minimum EMF emission by installing the low voltage cables and switchboard… Read more
Sep 26, 2016 | By Edvard Csanyi
PLC start up and checking procedures before applying the power
Prior to applying power to the system there are five important PLC start up and checking procedures to perform. User should make several final inspections of the hardware components and interconnections. PLC start up and checking procedures before applying the… Read more
Sep 23, 2016 | By Edvard Csanyi
8 steps to follow in power substation design and engineering
Building a new substation or retrofitting the old one is a complex process full of design and engineering tasks to be worked on. The main steps in substation design and engineering are as follows: Selection of a substation switching system:… Read more
Sep 21, 2016 | By Edvard Csanyi
Three-phase transformer connections and vector groups for beginners
In theory a three-phase transformer works like three separate single-phase transformers with shared limbs in which the magnetic circuit for the outer limbs is longer than for the centre limb. The voltage transformation is determined by the ratio between the… Read more
Sep 19, 2016 | By Edvard Csanyi
How to locate harmonic currents and where to control them?
On radial utility distribution feeders and industrial plant power systems, the main tendency is for the harmonic currents to flow from the harmonic-producing load to the power system source. This is illustrated in Figure 1. The impedance of the power… Read more
Sep 16, 2016 | By Edvard Csanyi
What is grounding and why do we ground the system and equipment?
The term grounding is commonly used in the electrical industry to mean both “equipment grounding” and “system grounding”. Equipment grounding means the connection of earth ground to non-current carrying conductive materials such as conduit, cable trays, junction boxes, enclosures, and motor… Read more
Sep 14, 2016 | By Edvard Csanyi
Power flow in MV radial network and calculation of voltage drop and loss
In three phase system the load for each phase should be the same. We call symmetrical load when the load of each phase is equal. In symmetrical circuit each phase has same configuration, so in drawing we can represent only… Read more
Sep 12, 2016 | By Edvard Csanyi
What a ground fault circuit interrupter does and what it does not do
A ground fault circuit interrupter (GFCI) monitors the current balance between the ungrounded “hot” conductor and the grounded conductor. As soon as the current flowing through the “hot” conductor is in the range of 4 to 6 milli-amperes more than the… Read more
Sep 09, 2016 | By Edvard Csanyi
When does exciting current inrush occur in power transformer?
When a transformer is initially energized, there is a phenomenon known as exciting current inrush. Although inrush currents are not generally as damaging as fault currents, the duration of exciting current inrush is on the order of seconds (as compared… Read more
Sep 07, 2016 | By Edvard Csanyi
4 essential implementations of protective relays in power systems
In this technical article, protective relays are categorized depending on the component which are protect: Generators Transmission lines Transformers, and Loads There are different protection schemes used for protecting generators depending on type of fault to which they are subjected…. Read more
Sep 05, 2016 | By Edvard Csanyi