Search

Premium Membership

Study specialized electrical engineering articles, papers & video courses in low/high voltage areas. Get 50% OFF on all courses at the EEP Academy with the Enterprise Plan.

Home / Technical Articles / Testing Procedures for HV Voltage Transformers
Testing Procedures for HV Voltage Transformers
Testing Procedures for HV Voltage Transformers (photo credit: hvcafrica.com)

Content:

  1. Equipment required for testing
  2. General inspection
  3. Insulation Resistance Test
  4. Polarity Test
  5. Transformer Turns ratio test

1. Equipment required

Following equipment is necessary to perform testings:

  • Polarity test kit
  • Megger 500-5000V
  • Ohmmeter
  • Multimeter
  • Autotransformers & Step-up transformers

Go up to the Content


2. General inspection

Mechanical checks

  • General visual inspection and compliance with the drawings and manuals.
  • Check nameplate ratings and HV, LV terminal markings.
  • Check that all parts of the transformer are properly assembled and tight.
  • Check the HV connections are tight.
  • Check the cable connections on the LV side and the markings.
  • Check the oil levels and inspect for leakage. (Where applicable)

Capacitor dividers type

Check that all parts of the transformers are properly assembled.


Electromagnetic type

Check the installation of different sections.

Electrical Checks

  • Check the equipment grounding (Continuity and connection)
  • Check the fuse rating of secondary side.
  • Perform the operation described in the following

Go up to the Content


Insulation Resistance Test

To obtain values as close as possible to the manufacturer’s specifications the insulators must be very clean. Select the megger range corresponding to the ratings of the equipment under test.

For Primary side, apply voltage depending on rating of voltage rating of VT.

  • For 6.6 kV VT (example), apply 2.5 kV and
  • For 132 kV VT (example), apply 5.0 kV.
Figure - Measurement between primary and secondary
Figure – Measurement between primary and secondary

Figure - Measurement between primary and ground
Figure – Measurement between primary and ground

Figure - Measurement between secondaries and between secondary and ground
Figure – Measurement between secondaries and between secondary and ground

Go up to the Content


Polarity Test

The polarity is checked using the flick method (application of direct current) and check of deflection on a bi-directional milliammeter. The test is also used to check primary and secondary circuit continuity.

  • When switch k is closed, the milliammeter pointer deflects positive.
  • When the circuit is opened, the milliammeter pointer deflects in the negative direction.
Figure - VT Polarity test
Figure – VT Polarity test

Go up to the Content


Transformer Turns ratio test

A variable AC source is applied on the primary side. The primary and secondary voltages are measured to determine the ratio V2/V1

Figure - Transformer Turns ratio test
Figure – Transformer Turns ratio test

Go up to the Content


132kv Substation

Go up to the Content

Reference: Contract specific procedure for testing of electrical equipment and 132kV OHL

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry facilities. Professional in AutoCAD programming.

20 Comments


  1. SADAK NAINGGOLAN
    Feb 08, 2021

    Thanks.


  2. YASEEN
    Nov 02, 2017

    THANKS FOR THIS INFORMATION


  3. Francois
    Jan 22, 2017

    This presenation is good but not all the info is 100%.
    For instance the identification of the VT Primary and secondary connections is wrong, Primary connections are labelled in Capital letters as A and N and secondary as a and n, your info might confuse first time students who wil perform these test.
    Also when you perform the insulation tests you remove the Primary N connection from earth when you test from Primary to earth and dont connnect it to the secondary as well because you want individual readings for each test performed to prove that each core is insulated on its own accordingly.
    the different secondary cores have different purposes and different VA’s , like for Metering and Protection purposes.
    When you test a CTPT unit it has a earth link in the secondary connection box that you have to remove before you start with the insulation tests.
    For the Polarity test 9 V or 12 V battery will be enough just make sure that the amp or Volt meter measures in mili amps( Volt), because due to the VT ratio you will get a miliamp or milivolt output.Use any quality galvano meter with a DC mili amp or volt selection to make your test easier.

    For the ratio test you can at least inject from 500-1000 V across the primary connections and measure output on secondary, these were tests performed on 11 kV to 132kV VTS the error was still within the spec’s allowed.But the Accuracy class was then from 0.2Cl to 0.5Cl.

    Long before the CT analyser or CPC 100 Voltano 100 Sverker 750/760 or 950 was build we used a self build injection set for mag curves that could inject max 1000 V and up to 5 amps that we used for Metering and Protection CT’s to do the mag curves and we used it for VT ratio test because it had enough VA to perform the tests.
    Edvard sorry hat I used your blog here but in the Electrical field we share our info because and help others that are new to this field ours.
    Regards
    Francois

Leave a Reply to Francois

Tell us what you're thinking... we care about your opinion!

  +  78  =  eighty two

Electrical Engineering Courses

Learn to design electrical power and industrial automation systems through professional video courses.
Protection testing