Search

Premium Membership ♕

Limited Time Offer: Save 15% on PRO Plan with discount code: LRN15 and study specialized LV/MV/HV technical articles and studies.

Home / Technical Articles / Underground substations – Out of sight, out of mind

Underground substations

Underground substations help to bring high voltage electricity directly into the city center. The stations are environmentally friendly, almost unnoticeable, and have none of the planning problems encountered by surface-built solutions.

Underground substation in urban area - Out of sight, out of mind
Underground substation in urban area - Out of sight, out of mind (It’s possible to tuck away 98% of a substation below ground level) - credit: ABB

Building new transformer substations in inner-city zones or expanding existing facilities is a challenging remit: Due to the lack of acceptance by the local community, the expense or a lack of space.

However, the best way of meeting the rising demand for energy is to bring high-voltage electricity directly into the city to ensure highly reliable power supplies at an affordable cost.

Bustling urban centers need efficient and reliable electricity, but usually do not have space for large electrical installations. Placing the substation underground reduces space requirements at downtown sites, since the free surface area can be used for other purposes, such as shopping malls or parks.

The purpose of underground substations is to provide all the functionality of a conventional substation while minimizing the area occupied above ground.

There is an increasing demand for compact and discreet transformer substations in city environments for urban development projects and other densely populated areas around the globe.

Underground substations are not a new idea and many such installations are already in operation.

Customer benefits include a near-invisible installation that blends into the surrounding landscape and is acceptable to the local community. The concept enables transformer substations to be integrated into any urban environment – underneath other buildings or building complexes such as shopping malls or in multi-storey car parks, beneath parks, sport stadiums and public squares as well as intersections or roundabouts.

Underground substations - Out of sight, out of mind
Underground substations – Out of sight, out of mind (credit: ABB)

A substation of this kind contains essential equipment such as:

  • Transformers,
  • Gas-insulated, high-voltage switchgear (GIS)
  • Medium-voltage switchgear,
  • Automation,
  • Protection and control systems,
  • Auxiliary equipment for station services,
  • AC and DC distribution boards,
  • Batteries,
  • Ventilation and air-conditioning systems and
  • Fire protection systems.

Reliability, redundancy and safety eg, through separation of fire loads by bulkheads, are vital attributes of underground substations.


During the initial planning work, certain restrictions have to be given particular attention, like temperature profiles of the surroundings, permissible equipment temperatures and heat dissipation, the space available in general, plus the space available for ventilation openings, the possible air velocity in air ducts and filters, the permitted noise emission levels, the composition and load-bearing characteristics of the ground, as well as the surrounding structures.

Lifting equipment inside of underground substation
Lifting equipment inside of underground substation (credit: ABB)

The above-ground footprint is required to be very small. In the sample concept, it accounts for a mere two percent of the substation’s total volume.

One important aspect to be considered is the optimization of the transportation and access routes. It must, for example, be possible to easily add or replace any piece of equipment including the station’s largest items, the power transformers.

Not least, human safety is of paramount importance. Although the stations are normally unmanned, redundant escape routes have to be provided on all levels. The concept also incorporates smoke-free zones such as the stairwells. Outside the substation, further safety aspects have to be taken into account as any potential hazards have to be confined to the station itself.

Switching and transformer-related noise emissions, that are audible outside, have to be kept within specified limits.

Reference // Substations that can hide in a city – Underground solution concepts by ABB

Premium Membership

Get access to premium HV/MV/LV technical articles, electrical engineering guides, research studies and much more! It helps you to shape up your technical skills in your everyday life as an electrical engineer.
More Information
author-pic

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry facilities. Professional in AutoCAD programming.

3 Comments


  1. Susan Molok
    Sep 05, 2018

    This web site is really helpful for us student.


  2. JAGADISH GAMPA
    Jan 11, 2016

    Dear EDVARD!

    Electrical Engineering Portal is very excellent site. From this site every person related to electrical trade are gaining more knowledge. It is very useful to our careers. Very Very Excellent articles. We have to spend lot of time to gain the knowledge. Please provide complete trouble shooting articles also. It is very useful to electrical engineers & technicians.

    Thank You very much for sharing.


  3. Manuel Bolotinha
    Jan 09, 2016

    In underground substations is recommended also to use medium voltage switchgear with GIS technology and gas insulated transformers up to 60 MVA(GIT) in order to reduce the space requires by the substation.
    GIS equipment and GIT may be installeded in the same roor, no separation being required.

Leave a Reply to JAGADISH GAMPA

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

ninety five  ⁄    =  19

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Courses - A hand crafted cutting-edge electrical engineering knowledge