Search

Premium Membership ♕

Save 20% with a coupon BLACKFRIDAY on the PRO Membership Plan and all courses at EEP Academy! Learn from experienced engineers!

Harmonic distortion of the AC power line in HVAC systems
Harmonic distortion of the AC power line in HVAC systems (photo credit: ke-next.de)

Causes of power line distortion

Most adjustable frequency drives operate by using a bridge rectifier to convert the incoming AC voltage to DC voltage (see figure 1). An inverter in the drive then converts the DC voltage into a precise output voltage and frequency to control the speed of the motor.

General block diagram of an adjustable frequency drive
Figure 1 – General block diagram of an adjustable frequency drive

Drives today use a diode bridge rectifier to convert the AC line power into a fixed‐voltage DC bus (see figure 2). A DC bus capacitor bank is then used to filter out the AC ripple.

Diode bridge rectifier on a PWM drive
Figure 2 – Diode bridge rectifier on a PWM drive

While this results in a very efficient drive, it can cause disturbances on the AC power line due to the way the drive draws AC current.

Current cannot flow from the rectifier into the DC bus until the input voltage is greater than the DC bus voltage. As shown in figure 3, this only happens for a very short period of time for each phase.

Input with high peak current
Figure 3 – Input with high peak current

This causes a non‐sinusoidal current flow created by the input stage of the drive. In order to transfer the energy required by the motor in such a short period of time, the peak current must be high.

Title:Harmonic Distortion of the AC Power Line – Danfoss
Format:PDF
Size:365 KB
Pages:7
Download:Right here | Video Courses | Membership | Download Updates
Harmonic Distortion of the AC Power Line
Harmonic Distortion of the AC Power Line – Danfoss

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

2 Comments


  1. Pavel Chernikov
    May 26, 2014

    Detail description see IEEE Std 519-1992 section 4


  2. mark lodovice
    May 25, 2014

    thanks for the news it is very useful to me

Leave a Reply to Pavel Chernikov

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

77  −  68  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Save 20% with coupon BLACKFRIDAY.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.