Search

Premium Membership ♕

Save 20% with a coupon BLACKFRIDAY on the PRO Membership Plan and all courses at EEP Academy! Learn from experienced engineers!

Home / Download Center / Electrical Engineering Books and Technical Guides / Power substation guides / Low voltage switchgear and controlgear technical guide

Considerations when building control systems and switchgear assemblies

Temperature rise

The temperature of the devices in the switchboard cabinet and that of touchable parts are important factors with respect to operational reliability, life span and personal safety.

Guide to low voltage switchgear and controlgear
Guide to low voltage switchgear and controlgear (photo credit: electricite-plus.com)

It depends among other things on the ambient temperature of the switchgear assembly, the heat flow via enclosures, if any, and/or air conditioning, the method of installation of devices (mutual heating, heat abduction, formation of hotspots), wiring (heat-flow via conductors) and last but not least the dissipated heat (load losses) of the devices.

Temperature rise limit values

The relevant standards such as IEC 60947-1 (low voltage switchgear) and IEC 60439-1 (Low voltage switchgear assemblies) define upper limits for the temperatures of the relevant constructive parts. IEC 60204 (Safety of machinery – Electrical equipment of machines) refers to IEC 60439-1.

Temperature-rise limit values in accordance with IEC 60947 and IEC 60439

PartTemperature-rise limits *1Reference (ambient) temperatureTemperature limit (absolute) *1
Metallic manual operating means15 … 25 K40 °C55 … 65 °C
Non-metallic manual operating means25 … 35 K40 °C65 … 75 °C
Metallic parts intended to be touched but not handheld30 … 40 K40 °C70 … 80 °C
Non-metallic parts intended to be touched but not hand-held40 … 50 K40 °C80 … 90 °C
Metallic surfaces not intended to be touched40 … 50 K40 °C80 … 90 °C
Non-metallic surfaces not intended to be touched50 … 60 K40 °C90 … 100 °C
Terminals for external connections (Cu silver- or nickelplated)70 … 80 K40 °C110 … 120 °C
*1 The higher values apply for used devices and for parts which are not intended to be touched or operated frequently respectively.

The permissible temperature rises or temperatures appear in some cases to be high, for example those for the temperature-rise of terminals. This limit value is based on the connection of conductor material with a permissible continuous insulation temperature of 70 °C.

The high temperature of the connection point itself is permissible as after only a short distance, the conductor temperature starts to decrease due to the heat flow from the terminal point via the connected line.

The conductor material (cable, busbar etc.) acts as a thermal aerial assisting in the heat dissipation process. Experience gained over many decades and with billions of terminal points confirms the correct choice of the limit values.

Typical decrease in conductor temperature
Typical decrease in conductor temperature with increasing distance from the terminal

Decisive for the functional reliability of devices, their life span or the risk of accidents, is not the temperature-rise but the absolute temperature.

The standards define temperature-rise limits for practical reasons so that tests can be performed in a laboratory environment. The reference ambient temperature in accordance with standards is 35 °C as an average over 24 hours with a maximum value of 40 °C.

If the ambient temperature around the devices exceeds these values in actual service – for example because they are installed in a switching cabinet – then their load must be reduced correspondingly so that the permissible absolute temperature values are observed.

The normal temperature range for devices in accordance with IEC 60947
The normal temperature range for devices in accordance with IEC 60947 is identical with the normal temperature range for switchgear assemblies in accordance with IEC 60439, in which the devices are installed.

This especially affects the temperatures of internal parts of devices in respect of the thermal stability of the materials used. For reduction factors, see manufacturers documentation.

Title:Low Voltage Switchgear and Controlgear – Technical Document by Rockwell Automation and authors: Dr. Werner Breer, Paul Hug, Urs Hunziker, Rey Kaltenrieder, Heinz Unterweger and Dr. Hans Weichert
Format:PDF
Size:5.7 MB
Pages:176
Download:Right here | Video Courses | Membership | Download Updates
Low-Voltage Switchgear and Controlgear - Technical Document
Low Voltage Switchgear and Controlgear – Technical Document (Allen-Bradley)

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

3 Comments


  1. hariom sharma
    Oct 12, 2022

    Electrical and Electronics devices are temperate sensitive and their performance also depends on temperature rise .Therefore due consideration to temperature sensitivity is essential.


  2. iledare lynda oifo
    Sep 02, 2014

    thinking of how we can make our protecting device 100% error free.


  3. ali surag
    May 04, 2014

    Very good notes and the switchgear system temperatuer it is very importent to the substation

Leave a Reply to iledare lynda oifo

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

  ⁄  8  =  1

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Save 20% with coupon BLACKFRIDAY.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.