Selecting relays to protect generator

Protection engineers must balance the expense of applying a particular relay or relay system against the consequences of losing a generator. The total loss of a generator may not be catastrophic if it represents a small percentage of the investment in an installation. However, the impact on service reliability and upset to loads supplied must be considered.

Generator protection application and relay selection guide
Generator protection application and relay selection guide

Damage to and loss of product in continuous processes can represent the dominating concern rather than the generator unit.

Accordingly, there is no standard solution based on the MW rating. However, it is rather expected that a 500 kW, 480 V, standby reciprocating engine will have less protection than a 400 MW base load steam turbine unit.

One possible common dividing point is that the extra CTs needed for current differential protection are less commonly seen on generators less than 2 MVA, generators rated less than 600 V and generators that are never paralleled to other generation.

This guide simplifies the process of selecting relays by describing how to protect against each type of external and internal fault or abnormal condition. Then, suggestions are made for what is considered to be minimum protection as a baseline.

After establishing the baseline, additional protection, as described in the section on Integrated Application Examples, may be added.

Low z grounded generator with sequential trip and sync check (j-case)
Low z grounded generator with sequential trip and sync check (j-case)

The subjects covered in this guide are as follows:

  • Ground Fault (50/51-G/N, 27/59, 59N, 27-3N, 87N)
  • Phase Fault (51, 51V, 87G)
  • Backup Remote Fault Detection (51V, 21)
  • Reverse Power (32)
  • Loss of Field (40Q and 40Z)
  • Thermal (49RTD)
  • Fuse Loss (60)
  • Overexcitation and Over/Undervoltage (24, 27/59)
  • Inadvertent Energization (50/27)
  • Negative-sequence Current and Voltage (46, 47)
  • Off-Frequency Operation (81O/U/ROC)
  • Sync Check (25) and Auto Synchronizing (25A)
  • Out of Step (78OOS)
  • Selective and Sequential Tripping
  • Integrated Application Examples
  • Application of BE1-11g Multifunction Relay System
  • Typical Settings

Ground Fault Protection

The following information and examples cover three impedance levels of grounding: low-, medium- and high-impedance grounding.

A low-impedance grounded generator is a generator that has zero or minimal impedance applied at the wye neutral point so that, during a ground fault at the generator HV terminals, ground current from the generator is approximately equal to three-phase fault current.

Ground-fault protection - generator low-impedance grounding
Ground-fault protection – generator low-impedance grounding

A medium-impedance grounded generator is a generator that has substantial impedance applied at the wye neutral point so that, during a ground fault, a reduced but readily detectable level of ground current, typically 100-500 A, flows.

A high-impedance grounded generator is a generator with a large grounding impedance so that, during a ground fault, a nearly undetectable level of fault current flows, making ground fault monitoring with voltagebased (e.g., third-harmonic voltage monitoring and fundamental frequency neutral-voltageshift monitoring) protection necessary.

The location of the grounding, generator neutral(s) or transformer also influences the protection approach.

Title:Generator Protection Application Guide – Basler Electric
Format:PDF
Size:962 KB
Pages:28
Download:Right here | Video Courses | Membership | Download Updates
Generator Protection Application Guide
Generator Protection Application Guide

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
50% Discount 💥 - Save 50% on all 90+ video courses with Enterprise Membership plan.

More Information

2 Comments


  1. Roberto Punzalan
    Feb 11, 2025

    I am interested in receiving more information about power generation and protection.


  2. Israel Goodluck
    Feb 15, 2021

    Really impressed!. Please how do I get premium membership and much more?

Leave a Reply to Roberto Punzalan

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

64  ⁄  32  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

EEP Hand-Crafted Video Courses

Check more than a hundred hand-crafted video courses and learn from experienced engineers. Lifetime access included.
Save 20% with coupon BLACKFRIDAY.
Experience matters. Premium membership gives you an opportunity to study specialized technical articles, online video courses, electrical engineering guides, and papers written by experienced electrical engineers.