MV Network Design
MV Network Design Book, prepared by Schneider Electric gives a great technical knowledge of MV network design and correct devices selection intended for medium voltage equipment and network designers.

This guide helps you to carry out the various calculations required to define and determine network characteristics, substation equipment dimensions and provides useful information enabling you to design your MV switchboard and other substation devices.
Exercise sections and answers:
- MV substation architectures
- MV substation architectures
- Industrial C13-200 MV substation
- Max. distance between surge arrester and MV equipment
- Calculation of MV cable cross-section
- Calculation of Isc
- CT s for MV metering
- CT s for MV protection
- Earth-fault relay settings
- Capacitors
Exercise #1 – MV substation architectures
To define //
- Type of LV or MV metering
- Architecture and choice of cubicles
- Type and rating of fuse that protects the transformer
Inputs //
- Consumer substation on energy supplier loop: 20kV
- 1 800kVA transformer with 20kV/400V secondary
- Short-circuit power 250 MVA
Answers and chosen substation equipment //
- 800 kVA with 20 kV = 23A < 45A
OK for LV metering
- 800 kVA with 410V = 1127A < 2000A
- 800 kVA < 1250 kVA
- MV Isc 20kV = 250MVA / 20kV / 1.732 = 7.2 kA rms
OK for standard equipment 24 KV 12.5 kA
- 800 kVA 20 kV transformer, UTE standard,
43A Solefuse chosen fuse rating

| Title: | MV Network Design Answer and Exercise Book by Schneider Electric |
| Format: | PDFs |
| Size: | 100 KB + 170 KB |
| Pages: | 31 + 37 |
| Download 1: | Here 🔗 (Get Premium Membership) | Video Courses | Download Updates |
| Download 2: | Here 🔗 (Get Premium Membership) | Video Courses | Download Updates |
Recommended – Biggest Mistakes in Analyzing Modern Substation Schematics
Thank you for sharing this opportunity and I am glad to connect to your esteemed organization.
I am really interested
it is necessary to insert in the diagram an inverter between the transformers and the generator
It’s a very helpful information. Thank You!
You’re welcome Kishor, I’m glad you find it useful.
I think it’s a very helpful information
Excelente práctica y aplicable información
Thanks, Right time right Article. Now I am working on big project there have 8 substation, I verified that design with the help of this Exercise .
Thanks it very useful
Thanks, Really useful.
Me interesa este tipo de ejemplos sobre arquitectura de una sub-estacion MV, pues es muy ilustrativo.
Valuable information! Thanks for sharing it!
Very helpful information, thank you
Where is the Design Guide? The only downloads I see are for the exercise book and the answer book, but not the actual guide.