Water Pipes for grounding
Water pipes have been used extensively in the past as a grounding electrode. Water pipe connections are not testable and are unreliable due to the use of tar coatings and plastic fittings.

City water departments have begun to specifically install plastic insulators in the pipelines to prevent the flow of current and reduce the corrosive effects of electrolysis. Since water pipes are continuous city wide, fault conditions in adjacent neighborhoods could backfeed current into sensitive equipment causing unintentional damage.
The NEC requires that at least one additional electrode be installed when using water metal pipes as an electrode.
There are six several additional requirements including //
- 10 ft of the water pipe is in direct contact with the earth
- Joints must be electrically continuous
- Water meters may not be relied upon for the grounding path
- Bonding jumpers must be used around any insulating joints, pipe, or meters
- Primary connection to the water pipe must be on the street side of the water meter
- Primary connection to the water pipe shall be within 5 ft of the point of entrance to the building
Reference // Standard Handbook for Electrical Engineers By Donald G. Fink, H. Wayne Beaty (Get it from Amazon)
Related electrical guides & articles
Premium Membership


Can I use galvanised pipe instead of rod to ground an electric fence?
I noticed the ground wire from my outside pipe was broken and te=wisted it back together.
I noticed the same on my gas meter not a good connection, called the utilities and nothing is done. Guess I wll have to do it myself.
Thank you so much to share this article. It contains important information. Keep writing to us.
At places like campgrounds, a solid metal pipe goes 3 feet into the ground. Places like that are perfectly acceptable for grounding. Imagine having to buy a copper rod for each site if pipes were an absolute no-no.
Yeah, could you even imagine? Grounding rods cost like a whole $8 and take like a whole MINUTE to install! However would we cope with having to buy ground rods?
In Europe, namely in Portugal, national wiring regulations no longer allowthe use of water pipes fo grounding purposes.
Nowadays is is useless to discuss this topic.
They have a ground wire on our water pipe and in Wisconsin. I was having issues and an electrician and electrical engineer somehow separated the water pipe with a piece of plexiglass. There was current running along all the pipes. After that was done the emf dropped to -0- on the water pipe measured on the living room floor. These guys also told me that the ground will also connect you to any wiring above or below ground and to neighbors dirty electric. Who do you call to do that as my electrician is retired.
Dear all
I have been using water pipes system as a ground for more than 10 years and it is perfect,here who.
As it mentioned above that the government changed the pipes to PPR type but in the same time they did not remove the old still pipes and it is covering an aria over 50 KM squire and rounding all the houses in my aria and very deep in the ground which is a good earth .another thing i used this ground as a neutral
when the neutral cable has been cut during the fitting with gadafi troops that they protecting his house and it works perfect with lights and small appliances like TV-VIDEOS-PLAY STATIONS-COMPUTERS.
But what is the damage to the water piping, pitting and corrosion if the ground isn’t connected close to the water meter?