Search

Black Friday Deal💥

Save 20% with a coupon BLCK20 on PRO Membership Plan and all courses at the EEP Academy! Learn from experienced engineers!

Lightning protection system

The function of a lightning protection system is to protect structures from fire or mechanical destruction and persons in the buildings from injury or even death. A lightning protection system consists of an external and an internal lightning protection system (presented in Figure 1).

Lightning protection guide 2015 by DEHN + SÖHNE
Lightning protection guide 2015 by DEHN + SÖHNE

The functions of the external lightning protection system are:

  1. To intercept direct lightning strikes via an air-termination system
  2. To safely conduct the lightning current to the ground via a down-conductor system
  3. to distribute the lightning current in the ground via an earth-termination system
Components of a lightning protection system
Figure 1 – Components of a lightning protection system

The function of the internal lightning protection system is to prevent dangerous sparking inside the structure.

This is achieved by establishing equipotential bonding or maintaining a separation distance between the components of the lightning protection system and other electrically conductive elements inside the structure.

Lightning equipotential bonding reduces the potential differences caused by lightning currents. This is achieved by connecting all isolated conductive parts of the installation directly by means of conductors or surge protective devices (SPDs) (Figure 2).

Lightning protection system (LPS)
Figure 2 – Lightning protection system (LPS)

The four classes of LPS I, II, III and IV are determined using a set of construction rules including dimensioning requirements which are based on the relevant lightning protection level. Each set comprises class-dependent (e.g. radius of the rolling sphere, mesh size) and class-independent (e.g. cross-sections, materials) requirements.

To ensure permanent availability of complex information technology systems even in case of a direct lightning strike, additional measures, which supplement the lightning protection measures, are required to protect electronic systems against surges.

These comprehensive measures are described in chapter 7 (lightning protection zone concept).

Title:Lightning protection guide 2015 by DEHN + SÖHNE
Format:PDF
Size:16.0 MB
Pages:489
Download:Right here | Video Courses | Membership | Download Updates
Lightning protection guide 2015 by DEHN + SÖHNE
Lightning protection guide 2015 by DEHN + SÖHNE

Premium Membership

Get access to premium HV/MV/LV technical articles, advanced electrical engineering guides, papers, and much more! It will help you to shape up your technical skills in your everyday life as an electrical engineer.
Black Friday Deal 💥 - Save 20% on Pro Membership Plan and all courses at EEP Academy with a discount code BLCK20

More Information

7 Comments


  1. kevin amsberry
    May 18, 2022

    I am receiving a patent 05/24/2022 which actually prevents lightning strikes. No more lightning rods. I am on LinkedIn with details. Kevin Amsberry


  2. Emmanuel Teddy
    Mar 30, 2022

    I paid a visit to a small industry where most of the structures are constructed by steel plates and some iron sheets. But no LPS was installed. The area is not so prone to lightning but the rare cases in past have been fatal. Is this recommended, considering the structures n human operators therein?


  3. Neal Sklodowski
    Mar 24, 2022

    Are lightning protection systems installed on all buildings. Are there parameters that would determine the need for a LPS?

    I am located in Hawaii and it appears that our three hotel towers do not have a system installed. Lightning is rare in Hawaii, but just wondering if an LPS is required.


  4. SANDEEP PATHARE
    Mar 15, 2021

    How do you decide LPS class or radius of sphere say for industrial installation.Say Ihave hihg mast of 30 mtr so which class I should select?


    • Noman Abdullah
      May 25, 2021

      Building Height Below 23mtr need Class-1 LPS system
      Building Height Over 23mtr need Class-2 LPS system


  5. H S GILL
    Nov 06, 2019

    Sir,
    Where should the lightening arrestors be located in a gas compressor plant?


  6. Mário Sotomaior
    Feb 08, 2017

    I found several times the ground conductor for lightning protection passing throw a iron galvanized pipe. As the pipe around de conductor is ferromagnetic this increases the indutance.
    Is this correct ?
    Thanks
    Mário

Leave a Reply to Neal Sklodowski

Tell us what you're thinking. We care about your opinion! Please keep in mind that comments are moderated and rel="nofollow" is in use. So, please do not use a spammy keyword or a domain as your name, or it will be deleted. Let's have a professional and meaningful conversation instead. Thanks for dropping by!

three  ⁄  one  =  

Learn How to Design Power Systems

Learn to design LV/MV/HV power systems through professional video courses. Lifetime access. Enjoy learning!

Subscribe to Weekly Newsletter

Subscribe to our Weekly Digest newsletter and receive free updates on new technical articles, video courses and guides (PDF).
EEP Academy Hand-Crafted Courses
ETAP technical webinars